ASHRAE 170: Complete Guide to Ventilation of Health Care Facilities
Guide to ASHRAE 170 ventilation for health care facilities: ventilation rates, pressure relationships, filtration, and temperature and humidity control.
ASHRAE 170: Complete Guide to Ventilation of Health Care Facilities
ASHRAE Standard 170 establishes ventilation requirements for health care facilities to control airborne contaminants, reduce infection risk, and maintain appropriate environmental conditions for patients, staff, and visitors. This standard addresses ventilation rates, air quality, filtration, temperature, humidity, and pressure relationships. Understanding ASHRAE 170 is essential for healthcare facility designers, infection control professionals, and facility managers.
The standard provides specific requirements for various health care spaces, including patient rooms, operating rooms, isolation rooms, and support spaces. It integrates with ASHRAE 62.1 while establishing enhanced requirements for healthcare applications. This comprehensive guide covers all major sections, requirements, and practical applications.
Introduction to ASHRAE 170
Purpose and Scope
ASHRAE Standard 170 serves multiple critical functions:
Infection Control:
- Reduce airborne transmission
- Control contamination
- Protect patients
- Protect staff
Environmental Control:
- Maintain appropriate conditions
- Support healing
- Ensure comfort
- Protect equipment
Code Compliance:
- Health care facility codes
- Building codes
- Regulatory requirements
- Certification programs
Scope
Applies to:
- Hospitals
- Outpatient facilities
- Long-term care
- Ambulatory care
- All health care facilities
Ventilation Requirements
Ventilation Rates
Patient Rooms:
Room Type | Outdoor Air (L/s·m²) | Outdoor Air (cfm/ft²) | Total Air (ACH) | Notes |
|---|---|---|---|---|
Patient room | 2.4 | 0.5 | 6 | Standard |
ICU | 2.4 | 0.5 | 6 | Intensive care |
Isolation, AII | 2.4 | 0.5 | 12 | Airborne isolation |
Isolation, PE | 2.4 | 0.5 | 12 | Protective environment |
Burn unit | 2.4 | 0.5 | 6 | Special care |
Nursery | 2.4 | 0.5 | 6 | Infant care |
Ventilation Rate Calculation:
Where:
- = Total airflow (m³/h or cfm)
- = Air changes per hour
- = Room volume (m³ or ft³)
Outdoor Air Calculation:
Where:
- = Outdoor airflow (L/s or cfm)
- = Outdoor air rate per area (L/s·m² or cfm/ft²)
- = Floor area (m² or ft²)
Operating Rooms:
Room Type | Outdoor Air (L/s·m²) | Outdoor Air (cfm/ft²) | Total Air (ACH) | Notes |
|---|---|---|---|---|
Operating room | 3.8 | 0.8 | 20 | Standard |
Cystoscopy | 3.8 | 0.8 | 20 | |
Delivery room | 3.8 | 0.8 | 20 | |
Procedure room | 3.8 | 0.8 | 15 | Minor procedures |
Recovery room | 2.4 | 0.5 | 6 | Post-operative |
Support Spaces:
Space Type | Outdoor Air (L/s·m²) | Outdoor Air (cfm/ft²) | Total Air (ACH) | Notes |
|---|---|---|---|---|
Emergency | 2.4 | 0.5 | 6 | |
Pharmacy | 2.4 | 0.5 | 6 | |
Laboratory | 2.4 | 0.5 | 6 | |
Sterile storage | 0.6 | 0.12 | 4 | |
Soiled workroom | 2.4 | 0.5 | 10 | |
Clean workroom | 2.4 | 0.5 | 4 | |
Autopsy | 2.4 | 0.5 | 12 |
Ancillary Spaces:
Space Type | Outdoor Air (L/s·m²) | Outdoor Air (cfm/ft²) | Total Air (ACH) | Notes |
|---|---|---|---|---|
Corridor | 0.6 | 0.12 | 2 | |
Waiting room | 2.4 | 0.5 | 6 | |
Toilet | 2.4 | 0.5 | 10 | |
Locker room | 2.4 | 0.5 | 6 | |
Storage | 0.6 | 0.12 | 2 |
Pressure Relationships
Pressure Requirements:
Space Type | Pressure Relationship | Notes |
|---|---|---|
Operating room | Positive | Protect from contamination |
Patient room | Neutral or positive | Standard |
Isolation, AII | Negative | Contain contaminants |
Isolation, PE | Positive | Protect patient |
Anteroom | Variable | Based on adjacent spaces |
Pharmacy | Positive | Protect medications |
Sterile storage | Positive | Protect supplies |
Soiled workroom | Negative | Contain contamination |
Autopsy | Negative | Contain odors |
Pressure Differential Requirements:
Space Type | Minimum (Pa) | Minimum (in. w.g.) | Typical (Pa) | Typical (in. w.g.) | Notes |
|---|---|---|---|---|---|
Operating room | 2.5 | 0.01 | 5-12 | 0.02-0.05 | Positive |
Isolation, AII | 2.5 | 0.01 | 5-12 | 0.02-0.05 | Negative |
Isolation, PE | 2.5 | 0.01 | 5-12 | 0.02-0.05 | Positive |
Anteroom | 2.5 | 0.01 | 5-12 | 0.02-0.05 | Variable |
Pressure Monitoring:
Monitoring Type | Requirement | Notes |
|---|---|---|
Continuous | Required for isolation | Real-time monitoring |
Alarms | Required | Visual and audible |
Recording | Recommended | Trend analysis |
Pressure Calculation:
Where:
- = Pressure differential (Pa)
- = Supply air pressure
- = Exhaust air pressure
Airflow Balance:
For positive pressure:
For negative pressure:
Typical Airflow Differences:
Pressure Type | Airflow Difference | Notes |
|---|---|---|
Positive | +10-15% | Supply > exhaust |
Negative | -10-15% | Exhaust > supply |
Neutral | ±5% | Balanced |
Air Quality Requirements
Filtration
Filtration Requirements:
Space Type | Minimum MERV | Enhanced MERV | Notes |
|---|---|---|---|
General | 7 | 8 | Standard spaces |
Patient care | 13 | 14 | Patient areas |
Operating room | 14 | 15 | Surgical areas |
Isolation, AII | 14 | 15 | Airborne isolation |
Isolation, PE | 17 (HEPA) | 17 (HEPA) | Protective environment |
ICU | 13 | 14 | Intensive care |
Emergency | 13 | 14 | Emergency care |
Pharmacy | 13 | 14 | Medication protection |
Filter Locations and Requirements:
Location | Minimum MERV | Enhanced MERV | Notes |
|---|---|---|---|
Outdoor air intake | 7 | 8 | First line of defense |
Recirculation (general) | 7 | 8 | Standard spaces |
Recirculation (patient) | 13 | 14 | Patient areas |
Final filter (OR) | 14 | 15 | Surgical areas |
Final filter (PE) | 17 (HEPA) | 17 (HEPA) | HEPA required |
Exhaust (AII) | 14 | 15 | Before discharge |
Filtration Efficiency by Particle Size:
MERV | 0.3-1.0 μm (%) | 1.0-3.0 μm (%) | 3.0-10.0 μm (%) | Notes |
|---|---|---|---|---|
7 | < 20 | < 20 | ≥ 20 | Standard |
13 | ≥ 75 | ≥ 80 | ≥ 90 | Patient care |
14 | ≥ 85 | ≥ 90 | ≥ 95 | Operating rooms |
17 (HEPA) | ≥ 99.97 | ≥ 99.97 | ≥ 99.97 | PE rooms |
Filter Installation Requirements:
Requirement | Specification | Notes |
|---|---|---|
Filter housing | Leak-tight | No bypass |
Filter mounting | Proper sealing | Gaskets required |
Access | Easy replacement | Maintenance access |
Monitoring | Pressure drop | Filter status |
Outdoor Air Quality
Requirements:
- Meet ASHRAE 62.1 requirements
- Enhanced filtration if needed
- Monitoring
- Treatment if required
Outdoor Air Quality Standards:
Contaminant | Maximum (μg/m³) | Treatment Required | Notes |
|---|---|---|---|
PM2.5 | 35 (24-hr) | MERV 13+ | Enhanced filtration |
PM10 | 150 (24-hr) | MERV 8+ | Standard filtration |
Ozone | 0.12 ppm (1-hr) | Filtration/adsorption | Enhanced treatment |
CO | 9 ppm (8-hr) | Usually acceptable | Standard |
Treatment Requirements:
If outdoor air exceeds limits:
Where:
- = Required removal efficiency
- = Acceptable limit
- = Outdoor concentration
Air Cleaning Systems:
System Type | Efficiency | Application | Notes |
|---|---|---|---|
Filtration | MERV 13-17 | Particles | Standard |
Adsorption | 80-95% | Gases, odors | Activated carbon |
UVGI | 90-99% | Microorganisms | Germicidal |
Combination | High | Multiple | Comprehensive |
Temperature and Humidity
Temperature Requirements
Space Temperature:
Space Type | Temperature Range (°C) | Temperature Range (°F) | Setpoint (°C) | Setpoint (°F) | Notes |
|---|---|---|---|---|---|
Patient room | 21-24 | 70-75 | 22.5 | 72.5 | Comfort |
Operating room | 20-24 | 68-75 | 20-22 | 68-72 | Lower for staff |
Isolation, PE | 22-24 | 72-75 | 23 | 73.5 | Higher for patient |
Nursery | 24-27 | 75-80 | 25.5 | 78 | Higher for infants |
ICU | 21-24 | 70-75 | 22.5 | 72.5 | Critical care |
Emergency | 21-24 | 70-75 | 22.5 | 72.5 | Emergency care |
Recovery | 21-24 | 70-75 | 22.5 | 72.5 | Post-operative |
Temperature Control Requirements:
Requirement | Specification | Notes |
|---|---|---|
Control accuracy | ±0.5°C | Precise control |
Deadband | 1-2°C | Energy savings |
Response time | < 5 minutes | Quick response |
Monitoring | Continuous | Real-time |
Humidity Requirements
Relative Humidity:
Space Type | RH Range (%) | Setpoint (%) | Notes |
|---|---|---|---|
Patient room | 30-60 | 45-50 | Standard |
Operating room | 20-60 | 50-55 | Lower for staff |
Isolation, PE | 30-60 | 45-50 | Standard |
Sterile storage | 35-60 | 45-50 | Material protection |
Nursery | 30-60 | 50-55 | Infant comfort |
ICU | 30-60 | 45-50 | Critical care |
Humidity Control Requirements:
Requirement | Specification | Notes |
|---|---|---|
Control accuracy | ±5% RH | Precise control |
Deadband | 5-10% RH | Energy savings |
Response time | < 10 minutes | Adequate response |
Monitoring | Continuous | Real-time |
Dew Point Requirements:
Maximum dew point: 16°C (61°F) for most spaces
Where:
- = Dew point (°C)
- = Temperature (°C)
- = Relative humidity (%)
Humidification Requirements:
Space Type | Humidification | Notes |
|---|---|---|
Patient room | Required | Winter months |
Operating room | Optional | Lower humidity acceptable |
Isolation, PE | Required | Patient comfort |
Nursery | Required | Infant comfort |
Dehumidification Requirements:
Space Type | Dehumidification | Notes |
|---|---|---|
All spaces | Required | Summer months |
Operating room | Required | Lower humidity |
Sterile storage | Required | Material protection |
Special Requirements
Airborne Infection Isolation (AII)
Requirements:
- Negative pressure
- 12 ACH minimum
- MERV 14 filtration
- Exhaust to outdoors
- Anteroom recommended
AII Room Design:
Component | Requirement | Notes |
|---|---|---|
Pressure | Negative | -2.5 to -12 Pa |
Ventilation | 12 ACH minimum | High air changes |
Filtration | MERV 14 | Exhaust filtration |
Exhaust | 100% to outdoors | No recirculation |
Anteroom | Recommended | Pressure buffer |
Monitoring | Continuous | Pressure, airflow |
AII Ventilation Calculation:
Where = Room volume (m³ or ft³)
Exhaust Requirements:
Requirement | Specification | Notes |
|---|---|---|
Exhaust location | Ceiling or high wall | Capture contaminants |
Exhaust rate | 100% of supply | Negative pressure |
Filtration | MERV 14 minimum | Before discharge |
Discharge | Away from intakes | Prevent re-entry |
Protective Environment (PE)
Requirements:
- Positive pressure
- 12 ACH minimum
- HEPA filtration
- Supply from clean source
- Anteroom required
PE Room Design:
Component | Requirement | Notes |
|---|---|---|
Pressure | Positive | +2.5 to +12 Pa |
Ventilation | 12 ACH minimum | High air changes |
Filtration | HEPA (MERV 17) | Final filter |
Supply | Clean source | Filtered air |
Anteroom | Required | Pressure buffer |
Monitoring | Continuous | Pressure, airflow |
PE Ventilation Calculation:
HEPA Filtration Requirements:
Requirement | Specification | Notes |
|---|---|---|
Efficiency | ≥ 99.97% @ 0.3 μm | HEPA standard |
Installation | Leak-tight | No bypass |
Testing | Annual | Performance verification |
Replacement | As needed | Based on pressure drop |
Operating Rooms
Requirements:
- Positive pressure
- 20 ACH minimum
- Laminar flow (optional)
- MERV 14 filtration
- Temperature control
Operating Room Design:
Component | Requirement | Notes |
|---|---|---|
Pressure | Positive | +2.5 to +12 Pa |
Ventilation | 20 ACH minimum | Very high air changes |
Filtration | MERV 14 minimum | Final filter |
Air distribution | Unidirectional (optional) | Laminar flow |
Temperature | 20-24°C (68-75°F) | Lower for staff |
Humidity | 20-60% | Lower for staff |
Operating Room Ventilation:
Laminar Flow Systems:
System Type | Coverage | Velocity | Notes |
|---|---|---|---|
Ceiling array | Operating table | 0.13-0.18 m/s | Unidirectional |
Full ceiling | Entire room | 0.13-0.18 m/s | Complete coverage |
Partial | Table area | 0.13-0.18 m/s | Focused coverage |
Laminar Flow Benefits:
- Reduced airborne contamination
- Lower infection rates
- Improved air quality
- Enhanced surgical environment
System Design
Air Distribution
Design Requirements:
- Unidirectional flow (OR)
- Proper mixing (patient rooms)
- Avoid short-circuiting
- Proper exhaust location
Air Distribution Types:
Space Type | Distribution Type | Notes |
|---|---|---|
Operating room | Unidirectional (laminar) | Optional, recommended |
Patient room | Mixing | Standard |
Isolation, AII | Mixing | Exhaust from ceiling |
Isolation, PE | Mixing | Supply from ceiling |
ICU | Mixing | Standard |
Supply Air Distribution:
Location | Application | Notes |
|---|---|---|
Ceiling | Most spaces | Standard |
High wall | Some isolation | Alternative |
Floor | Special cases | Rare |
Exhaust Air Location:
Location | Application | Notes |
|---|---|---|
Ceiling | Isolation, AII | Capture contaminants |
Low wall | Some spaces | Alternative |
Floor | Special cases | Rare |
Airflow Patterns:
Mixing Ventilation:
- Supply and return at ceiling
- Good mixing
- Uniform conditions
- Standard for most spaces
Unidirectional Flow:
- Supply from ceiling array
- Return at low level
- Laminar flow
- Operating rooms
Displacement Ventilation:
- Supply at floor
- Return at ceiling
- Natural convection
- Special applications
Controls
Control Requirements:
- Pressure monitoring
- Alarms
- Interlocks
- Status indication
Control Systems:
Control Type | Requirement | Notes |
|---|---|---|
Pressure | Continuous monitoring | Isolation rooms |
Temperature | Precise control | ±0.5°C |
Humidity | Precise control | ±5% RH |
Ventilation | Flow monitoring | Verify rates |
Filtration | Status monitoring | Filter condition |
Alarm Requirements:
Alarm Type | Trigger | Response | Notes |
|---|---|---|---|
Pressure loss | < Minimum | Immediate | Isolation rooms |
Temperature | Out of range | Alert | Comfort |
Humidity | Out of range | Alert | Comfort |
Filter | High pressure drop | Maintenance | Replacement needed |
System failure | Equipment failure | Immediate | Critical |
Interlock Requirements:
Interlock | Function | Notes |
|---|---|---|
Pressure | Maintain differential | Isolation rooms |
Exhaust | Start before supply | Negative pressure |
Supply | Start before exhaust | Positive pressure |
Emergency | Override normal | Emergency mode |
Redundancy
Requirements:
- Critical systems
- Backup systems
- Emergency power
- Reliability
Redundancy Requirements:
System Type | Redundancy Level | Notes |
|---|---|---|
Operating room | N+1 | Backup system |
ICU | N+1 | Backup system |
Isolation, PE | N+1 | Backup system |
Patient rooms | Standard | No redundancy |
Support spaces | Standard | No redundancy |
Emergency Power Requirements:
System Component | Emergency Power | Notes |
|---|---|---|
Operating room | Required | Critical |
ICU | Required | Critical |
Isolation, PE | Required | Critical |
Patient rooms | Required | Life safety |
Support systems | Required | Essential |
Reliability Requirements:
System | Uptime Requirement | Notes |
|---|---|---|
Operating room | 99.9% | Critical |
ICU | 99.9% | Critical |
Isolation rooms | 99.5% | Important |
Patient rooms | 99% | Standard |
Support spaces | 95% | Standard |
Additional Requirements
Air Change Rate Verification
Testing Requirements:
Test Type | Frequency | Method | Acceptance | Notes |
|---|---|---|---|---|
Airflow measurement | Initial | Flow hood | ±10% of design | All systems |
Air change calculation | Initial | Volume × ACH | Per specification | Verification |
Pressure testing | Initial | Manometer | Per specification | Isolation rooms |
Periodic testing | Annual | Flow measurement | Per specification | Ongoing |
Airflow Measurement:
Where:
- = Air changes per hour
- = Measured airflow (m³/min or cfm)
- = Room volume (m³ or ft³)
System Performance
Performance Metrics:
Metric | Target | Measurement | Notes |
|---|---|---|---|
Ventilation rate | Per specification | Flow measurement | All spaces |
Pressure differential | Per specification | Pressure measurement | Isolation rooms |
Filtration efficiency | Per specification | Filter testing | All filters |
Temperature control | ±0.5°C | Temperature measurement | All spaces |
Humidity control | ±5% RH | Humidity measurement | All spaces |
Performance Verification:
Verification Type | Method | Frequency | Notes |
|---|---|---|---|
Initial | Testing | At completion | All systems |
Periodic | Testing | Annual | Ongoing |
Continuous | Monitoring | Real-time | Critical systems |
Practical Application Examples
Example 1: Operating Room
Room:
- Operating room: 50 m² (538 ft²)
- Height: 3 m (10 ft)
- Volume: 150 m³ (5,300 ft³)
Requirements:
- Outdoor air: 3.8 L/s·m²
- Total air: 20 ACH
- Positive pressure: +5 Pa
- MERV 14 filtration
- Temperature: 20-24°C
Calculations:
Outdoor air: L/s (402 cfm)
Total air: m³/h (1,767 cfm)
Supply air: 3,000 m³/h (1,767 cfm) Exhaust air: 2,850 m³/h (1,678 cfm) (maintains positive pressure)
System:
- Dedicated system
- MERV 14 final filter
- Pressure monitoring
- Temperature control
Example 2: Isolation Room (AII)
Room:
- Isolation room: 25 m² (269 ft²)
- Height: 3 m (10 ft)
- Volume: 75 m³ (2,650 ft³)
Requirements:
- Outdoor air: 2.4 L/s·m²
- Total air: 12 ACH
- Negative pressure: -5 Pa
- MERV 14 filtration
- Anteroom
Calculations:
Outdoor air: L/s (127 cfm)
Total air: m³/h (530 cfm)
Supply air: 800 m³/h (471 cfm) Exhaust air: 900 m³/h (530 cfm) (maintains negative pressure)
System:
- Dedicated exhaust
- MERV 14 exhaust filter
- Pressure monitoring
- Anteroom with pressure control
Example 3: Protective Environment (PE)
Room:
- PE room: 25 m² (269 ft²)
- Height: 3 m (10 ft)
- Volume: 75 m³ (2,650 ft³)
Requirements:
- Outdoor air: 2.4 L/s·m²
- Total air: 12 ACH
- Positive pressure: +5 Pa
- HEPA filtration
- Anteroom
Calculations:
Outdoor air: L/s (127 cfm)
Total air: m³/h (530 cfm)
Supply air: 900 m³/h (530 cfm) Exhaust air: 800 m³/h (471 cfm) (maintains positive pressure)
System:
- Dedicated supply
- HEPA final filter
- Pressure monitoring
- Anteroom with pressure control
Best Practices
Design Practices
System Design:
- Exceed minimum requirements
- Consider redundancy for critical spaces
- Plan for maintenance access
- Document all systems
Air Distribution:
- Proper diffuser selection
- Avoid short-circuiting
- Optimize airflow patterns
- Consider local requirements
Controls:
- Reliable control systems
- Continuous monitoring
- Alarm systems
- Status indication
Operation Practices
Regular Testing:
- Airflow verification
- Pressure testing
- Filter performance
- System efficiency
Performance Monitoring:
- Continuous monitoring
- Trend analysis
- Performance tracking
- Issue identification
Maintenance:
- Regular filter replacement
- System cleaning
- Equipment maintenance
- Performance verification
Documentation:
- Test reports
- Maintenance records
- Performance data
- Issue tracking
Compliance and Certification
Code Compliance
Requirements:
- Meet ASHRAE 170 requirements
- Building code compliance
- Health department approval
- Certification programs
Verification:
- Design review
- Construction inspection
- Performance testing
- Documentation review
Certification Programs
Programs:
- Joint Commission
- CMS (Centers for Medicare & Medicaid Services)
- State health departments
- Facility-specific requirements
Conclusion
ASHRAE Standard 170 provides comprehensive ventilation requirements for health care facilities. Key aspects include:
Ventilation Requirements:
- Ventilation rates by space type
- Outdoor air requirements
- Total air changes
- Air distribution
Air Quality:
- Filtration requirements
- Outdoor air quality
- Monitoring requirements
- Treatment systems
Environmental Control:
- Temperature requirements
- Humidity requirements
- Pressure relationships
- Control systems
Special Requirements:
- Isolation rooms (AII)
- Protective environments (PE)
- Operating rooms
- Critical care spaces
By understanding and applying ASHRAE 170, designers can create safe and effective health care environments that support infection control, protect patients and staff, and maintain appropriate environmental conditions for healing and care delivery.