DIN EN 12831 Heating Load Dashboard

Multi-room · multi-floor design heat load (SI units)

DIN EN 12831-1
Total Heat Load Φ_HL
0.64 kW
637 W
Transmission Φ_T
0.36 kW
57%
Ventilation Φ_V
0.27 kW
43%
Reheat Φ_RH
0.00 kW
32 W/m² avg

Building

Ventilation

Building elements

TypeBoundaryOrient.A (m²)U (W/m²K)
Library:
Library:
Library:

Living room — Φ_HL

637 W
32 W/m² · 20 m² · θint 20°C
Transmission Φ_T365 W
Ventilation Φ_V272 W
Element losses
wall (N) · f=1.00127 W
window (S) · f=1.00110 W
floor (N) · f=0.50128 W
Air: 25 m³/hinf 9 · min 25
Orientation
NSEW

2 external elements

Method — DIN EN 12831-1 (design heat load)

ΦHL = ΦT + ΦV + ΦRH. Transmission ΦT = Σ (U+ΔUTB)·A·f·(θint−θe) with temperature-adjustment factor f per boundary (external f=1, ground f=1.45·(θint−θm,e)/(θint−θe), unheated and adjacent-room by temperature ratio). Ventilation ΦV = 0.34·V̇·(θint−θe), V̇ = max(2·V·n50·e·ε, nmin·V). Heating design ignores solar gains; orientation drives wind-shielding and documentation.