VAV Box Calculator


Input Parameters

Unit System

Results

VAV Box Sizing

1,111
Required Airflow CFM
5
Turndown Ratio
0
Reheat Required BTU/hr

VAV Performance

Required Airflow1,111 CFM(100%)
Turndown Ratio5 (20%)
Reheat0 BTU/hr(0%)

VAV Analysis

Calculation Steps

1

Calculate Temperature Difference

Formula:
ΔT=TroomTsupply\Delta T = T_{room} - T_{supply}
Calculation:
ΔT=7555\Delta T = 75 - 55
Result:
20.0 °F20.0 \text{ °F}
2

Calculate Required Airflow

Formula:
CFM=QBTU/hr1.08×ΔTCFM = \frac{Q_{BTU/hr}}{1.08 \times \Delta T}
Calculation:
CFM=24000.001.08×20.0CFM = \frac{24000.00}{1.08 \times 20.0}
Result:
1111.11 CFM1111.11 \text{ CFM}
3

Calculate Turndown Ratio

Formula:
Turndown=CFMmaxCFMminTurndown = \frac{CFM_{max}}{CFM_{min}}
Calculation:
Turndown=1000.00200.00Turndown = \frac{1000.00}{200.00}
Result:
5.00 5.00 \text{ }